Hi_Hi_Lim; Hi_Hi_Pri - Honeywell Series A User Manual

Fieldbus interface module
Hide thumbs Also See for Series A:
Table of Contents

Advertisement

Remarks

HI_HI_LIM

Classification
Description
FF Data Type
Range
Usage
Length
Valid Views
Storage
Remarks

HI_HI_PRI

Classification
Description
FF Data Type
Range
Usage
R400
Experion PKS Series A Fieldbus Interface Module User's Guide
July 2010
11.1. Standard Function Block Parameters
Read Only
The Data type consists of data that describes floating point
alarms. It uses the following five elements.
1 Unacknowledged
2 Alarm State
3 Time Stamp
4 Subcode
5 Value
Simple Variable
Defines the high high alarm limit setting in engineering
units.
Float
PV_SCALE, + infinity
C/Contained
4
VIEW_4
Static
Initial value is + infinity
Simple Variable
Defines priority of the high high alarm.
Unsigned 8
0 to 63
C/Alert Priority
Honeywell
11. Appendix B
449

Advertisement

Table of Contents
loading

This manual is also suitable for:

Experion pks series a

Table of Contents