Advertisement

5) Adjusting analog command voltages
To use external analog setting (VIB) or feedback input (VIA), perform voltage-scaling adjustments as
required. See Section 6.5.2 for further details.
If the feedback input data is too small, voltage-scaling adjustment data can also be used for gain adjustment.
Example of VIB terminal setting
(60Hz)
(0Hz)
0V
0%
6) Setting the time elapsed before PID control starts
You can specify a waiting time for PID control to prevent the inverter from starting PID control before the
control system becomes stable, for example, after start-up.
The inverter ignores feedback input signals, carries out operation at the frequency determined by the amount
of processing for the period of time specified with
the specified time.
Example of VIA terminal setting
(voltage input)
(60Hz)
(0Hz)
0V
10V
0%
100%
F-49
Example of VIA terminal setting
(current input)
(60Hz)
10V
4mA
(0Hz)
100%
20%
and enters the PID control mode after a lapse of
E6581158
20mA
100%
6