Calorific values of the inverter and the required ventilation
About 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC to
AC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the
interior of the cabinet must be ventilated and cooled.
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantity
when operating in a sealed cabinet according to motor capacity are as follows.
1
Voltage class
Single-phase
200V class
Single-Phase
200V class
Three-Phase
400V class
Notes
1)
2)
Panel designing taking into consideration the effects of noise
The inverter generates high frequency noise. When designing the control panel setup, consideration must be
given to that noise. Examples of measures are given below.
• Wire so that the main circuit wires and the control circuit wires are separated. Do not place them in the
same conduit, do not run them parallel, and do not bundle them.
• Provide shielding and twisted wire for control circuit wiring.
• Separate the input (power) and output (motor) wires of the main circuit. Do not place them in the same
conduit, do not run them parallel, and do not bundle them.
• Ground the inverter ground terminals (
• Install surge suppressor on any magnetic contactor and relay coils used around the inverter.
• Install noise filters if necessary.
Operating motor
capacity
kW
0.2
0.4
0.75
VFS11S-
1.5
2.2
0.2
0.4
0.55
0.75
1.5
VFS11-
2.2
3.7
5.5
7.5
11
15
0.4
0.75
1.5
2.2
3.7
VFS11-
5.5
7.5
11
15
The heat loss for the optional external devices (input reactor, DC reactor, radio noise reduction filters,
etc.) is not included in the calorific values in the table
Case of 100% Load Continuation operation.
Calorific Values
Carrier
Carrier
Inverter type
frequency
frequency
4kHz
12kHz
2002PL
23
29
2004PL
47
60
2007PL
74
88
2015PL
142
169
2022PL
239
270
2002PM
21
26
2004PM
43
54
2005PM
50
54
2007PM
67
79
2015PM
131
150
2022PM
168
195
2037PM
330
374
2055PM
450
510
2075PM
576
635
2110PM
750
820
2150PM
942
1035
4004PL
30
42
4007PL
44
57
4015PL
77
99
4022PL
103
134
4037PL
189
240
4055PL
264
354
4075PL
358
477
4110PL
490
650
4150PL
602
808
).
A-26
E6581158
Amount of forcible air
Heat discharge surface
cooling ventilation re-
area required for sealed
3
quired (m
/min)
storage cabinet(m
0.23
0.8
0.29
1.0
0.40
1.4
0.60
2.1
0.80
2.8
0.23
0.8
0.29
1.0
0.32
1.1
0.40
1.4
0.60
2.1
0.80
2.8
1.2
4.3
1.7
6.1
2.3
8.1
3.4
12.0
4.6
16.0
0.32
1.1
0.40
1.4
0.60
2.1
0.80
2.8
1.2
4.3
1.7
6.1
2.3
8.1
3.4
12.0
4.6
16.0
2
)