Preset-Speed Operation (Speeds In 15 Steps - Toshiba TOSVERT VF-S11 Instruction Manual

New global standard inverter
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

2) Inverter over load characteristics
Set to protect the inverter unit. Cannot be changed or turned off by parameter setting.
To prevent the inverter overload trip function (
tion level (
5

5.14 Preset-speed operation (speeds in 15 steps)

• Function
A maximum of 15 speed steps can be selected just by switching an external contact signal. Multi-speed
frequencies can be programmed anywhere from the lower limit frequency
When fire-speed control is assigned to the terminal board, the function of setting fire-speed operation frequencies
is assigned to
See 6.11.2, "Fire-speed control.
[Setting method]
1)
Run/stop
The starting and stopping control is done from the terminal board.
Title
Note: If speed commands (analog signal or digital input) are switched in line with preset-speed operations, select
the terminal board using the frequency setting mode selection
) or increase the acceleration time (
Inverter overload
Time [sec]
60
0
Inverter overload protection characteristics
*
To protect the inverter, overload trip activates in a short period of time when output cur-
rent reaches 150% or higher.
-
: Preset-speed operation frequencies 1-7
-
: Preset-speed operation frequencies 8-15
.
.
Function
Command mode selection
) from being activated too easily, lower the stall preven-
) or deceleration time (
100% = inverter rated output current
110%
150%
Adjustment range
0: Terminal board
1: Operation panel
E-26
E6581158
).
Output current [%]
to the upper limit frequency
Setting value
0
.
See 3) or 5.4