Sink logic/source logic (When the inverter's internal power supply
is used)
Current flowing out turns control input terminals on. These are called sink logic terminals. (Type: -AN/-WN).
The general used method in Europe is source logic in which current flowing into the input terminal turns it
on (Typ: -WP).
Sink logic terminals and source logic terminals are sometimes referred to as minus common terminals and
positive common terminals, respectively.
Each logic is supplied with electricity from either the inverter's internal power supply or an external power
supply, and its connections vary depending on the power supply used.
2
Examples of connections when the inverter's internal power supply is used
Slide switch SW1:SINK
Sink logic
Output
Common
Common
Input
Programmable
controller
Slide switch SW1:SOURCE
24V
DC
Input
F
CC
24V
D
Output
P24
OUT
NO
CC
Programmable
Inverter
controller
B-12
E6581158
Source logic
24V
DC
Input
P24
Common
Output
F
24V
DC
Output
P24
OUT
NO
Input
Common
CC
Inverter

Hide quick links: