Toshiba TOSVERT VF-S11 Instruction Manual page 204

New global standard inverter
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

(Continued)
Item displayed
Torque
Torque current
Inverter load factor
PBR cumulative
load factor
Input power
Output power
Operation fre-
quency
Input terminal
Note 4
8
Note 5
Output terminal
CPU1 version
CPU2 version
Memory version
PID feedback
Frequency com-
mand value (PID-
computed)
(Continued overleaf)
Key
LED
Communi-
cation No.
operated
display
FE18
FE20
FE27
FE25
FE29
FE30
FE00
FE06
FE07
FE08
FE73
FE09
FE22
FE15
H-8
Description
The torque at the occurrence of a trip (%) is
displayed.
The torque current (%/A) at the occurrence of a
trip is displayed.
The inverter load factor (%) at the occurrence of a
trip is displayed.
The cumulative load factor (%) of the resistor at
the occurrence of a trip is displayed.
The inverter input power (kW) at the occurrence of
a trip is displayed.
The inverter output power (kW) at the occurrence
of a trip is displayed.
The inverter output frequency (Hz/free unit) at the
occurrence of a trip is displayed.
The ON/OFF statuses of the control input termi-
nals (F, R, RES, S1, S2, S3, VIB and VIA) are dis-
played in bits.
ON:
OFF:
VIA
VIB
S3
S2
The ON/OFF status of each of the control signal
output terminals (RY, OUT and FL) at the occur-
rence of a trip is displayed in bits.
ON:
OFF:
FL
The version of the CPU1 is displayed.
The version of the CPU2 is displayed.
The version of the memory mounted is displayed.
The PID feedback value at the occurrence of a trip
is displayed. (Default setting: unit Hz)
The PID-computed frequency command value at
the occurrence of a trip is displayed. (Default set-
ting: unit Hz)