Terminal
Input/output
symbol
F
Input
R
Input
RES
Input
S1
Input
S2
Input
S3
Input
External 24Vdc power input
Input
PLC
When the source logic is used, a common
(common)
terminal is connected.
Common to
Control circuit's equipotential terminal (3
CC
Input/output
terminals)
P
Output
Analog input setting power output
Multifunction programmable analog input.
Factory default setting: 0~10Vdc and
0~60Hz frequency input.
The function can be changed to
4~20mAdc (0~20mA) current input by flip-
ping the slide switch to the I position.
VIA
Input
By changing parameter setting, this termi-
nal can also be used as a multifunction
programmable contact input terminal.
When using the sink logic, be sure to in-
sert a resistor between P24-VIA (4.7
kΩ
to the V position.
Function
Shorting across F-CC causes
forward rotation; open causes slow-
down and stop. (When ST is always
ON)
Shorting across R-CC causes
reverse rotation; open causes slow-
down and stop. (When ST is always
ON)
Shorting across RES-CC causes a
held reset when the inverter protector
function is operating. Note that when
the inverter is operating normally, it
will not operate even if there is a
short across RES-CC
Shorting across S1-CC causes
preset speed operation.
Shorting across S2-CC causes
preset speed operation.
Shorting across S3-CC causes
preset speed operation.
/2 W). Also turn the VIA slide switch
B-9
Electrical
Inverter internal circuits
specifications
No voltage
contact input
24Vdc-5mA or less
PLC
*Sink/Source/PLC
selectable using
SW1
F S3
Factory default setting
WN, AN type : SINK side
WP type : SOURCE side
24VDC
(Insulation resis-
tance: DC50V)
10Vdc
(permissible load
current: 10mAdc)
10Vdc
(internal impedance:
30kΩ)
4-20mA
(internal impedance:
250Ω)
E6581158
24V
SW1
PLC
SINK
SOURCE
2
820
4.7K
CC