Toshiba TOSVERT VF-S11 Instruction Manual page 245

New global standard inverter
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

Table of output terminal functions 3
Function
Code
No.
35
FCVIBN
Inversion of frequency VIB selection
36
FLR
Fault signal (put out also at the time of a retry)
37
FLRN
Inversion of failure signal (put out also at the time
of a retry)
38
OUT0
Specified data output 1
39
OUT0N
Inversion of specified data output 1
40
OUT1
Specified data output 2
41
OUT1N
Inversion of specified data output 2
42
COT
Cumulative operation time alarm
43
COTN
Inversion of cumulative operation time alarm
44
LTA
Calculation for life alarm
45
LTAN
Inversion of calculation for life alarm
46
BR
Braking sequence output
47
BRN
Inversion of braking sequence output
48
LI1
F terminal input signal
49
LI1N
Inversion of F terminal input signal
50
LI2
R terminal input signal
51
LI2N
Inversion of R terminal input signal
52
PIDF
Signal in accordance of frequency command
53
PIDFN
Inversion of signal in accordance of frequency
command
54
MOFF
Undervoltage detection
55
MOFFN
Inversion of undervoltage detection
56-253
Disabled
Invalid settings, always OFF (ignored)
254
AOFF
Always OFF
255
AON
Always ON
Function
Inversion of FCVIB
ON: When inverter trips or retries
OFF: When inverter does not trip or retry
Inversion of FLR
ON: Specified data from remote control FA50:
OFF: Specified data from remote control FA50:
Inversion of OUT0 setting
ON: Specified data from remote control FA50:
OFF: Specified data from remote control FA50:
Inversion of OUT1 setting
ON: Cumulative operation time is equal to or
OFF: Cumulative operation time is shorter than
Inversion of COT
ON: Calculation for life time is equal to or longer
ON: Calculation for life time is shorter than the
Inversion of LTA
ON: Braking retention signal
OFF: Braking release signal
Inversion of BR
ON: The signal input to F terminal is ON
OFF: The signal input to F terminal is OFF
Inversion of LI1
ON: The signal input to R terminal is ON
OFF: The signal input to R terminal is OFF
Inversion of LI2
ON: Frequency commanded by
OFF: Frequency commanded by
Inversion of PIDF setting
ON: Undervoltage detected
OFF: Other than undervoltage
Inversion of MOFF
Invalid settings, always OFF (ignored)
Always OFF
Always ON
K-19
E6581158
Action
BIT0= 1
BIT0= 0
BIT1= 1
BIT1= 0
longer than
than the preset time
preset time
and that by VIA show the same
value.
and that by VIA show different
values.
or
or
11