[Selection 1: Setting by automatic torque boost]
This is the easiest of the available methods. It conducts vector control and auto-tuning at the same time.
Set the automatic torque boost
(Automatic torque boost + auto-tuning)
Set the automatic torque boost
(Sensorless vector control + auto-tuning).
Set the automatic torque boost
(Energy-saving + auto-tuning)
See Section 5.2 for details of the setting method.
[Selection 2: Setting sensorless vector control and auto-tuning independently]
This method sets sensorless vector control or automatic torque boost, and auto-tuning independently.
Specify the control mode selection parameter (
Set the auto-tuning parameter
(Auto-tuning enabled)
[Parameter setting]
Title
Function
Auto-tuning
Set
to
.
to
to
to
) and then set auto-tuning.
to
Adjustment range
0: Auto-tuning disabled (use of internal parameters)
1: Application of individual settings of
execution: 0)
2: Auto-tuning enabled (after execution: 0)
F-51
E6581158
Default setting
(after
0
6