Output frequency [Hz]
6
6.2.2
• Function
Parameter setting
*
Note: When using the VIA terminal as a contact input terminal, be sure to turn the VIA slide switch to the V
=
(Reverse)]: If an F command and an R command are entered simultaneously,
the motor will run in the reverse direction.
Set frequency
0
Set frequency
Run forward signal
Run backward signal
Changing the functions of VIA and VIB terminals
: VIA/VIB terminal function selection
This parameter allows you to choose between signal input and contact signal input for the VIA and VIB
terminals.
Title
Function
Analog/contact input
function selection
(VIA/VIB terminal)
When using the VIA and VIB terminals as contact input terminals in sink logic connection, be sure to
insert a resistor between the P24 terminal and the VIA/VIB terminals. (Recommended resistance: 4.7kΩ-
1/2W)
position.
Adjustment range
0: VIA - analog input VIB - anolog input
1: VIA - anolog input VIB - contact input (Sink)
2: VIA - analog input VIB - contact input (Source)
3: VIA - contact input (Sink) VIB - contact input
(Sink)
4: VIA - contact input (Source) VIB - contact input
(Source)
F-6
E6581158
Forward run
Time [s]
Reverse run
ON
OFF
ON
OFF
Default setting
0