Toshiba TOSVERT VF-S11 Instruction Manual page 167

New global standard inverter
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

6.19.7 Control mode for small current
: Small current trip/alarm selection
: Small current detection current
: Small current detection time
• Function
The
parameter allows the inverter to be tripped if a current smaller than the
specified value flows for more than the
detection time to tripping. Trip information is displayed as "
= : No tripping (Failure signal FL not activated).
A small current alarm can be put out by setting the output terminal function selection parameter.
= : The inverter will trip (Failure signal FL activated) if a current below the current set with
flows for the period of time specified with
Title
Small current trip/alarm selection
Small current detection current
Small current detection time
-specified time. When tripping is selected, enter the
Function
F-65
".
.
Adjustment range
0: Alarm only
1: Tripping
0-100 (%)
0-255 [sec]
E6581158
-
6
Default setting
0
0
0