Toshiba TOSVERT VF-S11 Instruction Manual page 49

New global standard inverter
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

Terminal
Input/output
symbol
VIB
Input
2
FM
Output
P24
Output
OUT
Output
NO
FLA
FLB
Output
FLC
Function
Multifunction programmable analog input.
Standard default setting: 0~10Vdc input
and 0~60Hz frequency
By changing parameter setting, this termi-
nal can also be used as a multifunction
programmable contact input terminal.
When using the sink logic, be sure to in-
sert a resistor between P24 and VIB. (4.7
kΩ
/2 W)
Multifunction programmable analog out-
put. Standard default setting: output fre-
quency. Connect a 1mAdc full-scale am-
meter or 7.5Vdc (10Vdc)-1mA full-scale
voltmeter.
The function can be changed to 0-20mAdc
(4-20mA) current input by flipping the FM
slide switch to the I position.
24Vdc power output
Multifunction programmable open collector
output. Standard default settings detect
and output speed reach signal output fre-
quencies.
Multifunction output terminals to which two
different functions can be assigned.
The NO terminal is an isoelectric output
terminal. It is insulated from the CC termi-
nal.
By changing parameter settings, these
terminals can also be used as multifunc-
tion programmable pulse train output ter-
minals.
Multifunction programmable relay contact
output. Contact ratings: 250 Vac-1A(cosφ=1),
30Vdc-0.5A, 250Vac-0.5A(cosφ=0.4). De-
tects the operation of the inverter's protection
function.
Contact across FLA-FLC is closed and FLB-
FLC is opened during protection function op-
eration.
Electrical
specifications
10Vdc
(internal imped-
ance: 30kΩ)
1mA full-scale DC
ammeter or 7.5Vd
(10Vdc)1mA full-
scale DC voltmeter
0-20mA (4-20mA)
full-scale DC am-
meter
24Vdc-100mA
O pe n co llector o utp ut
24Vdc-50mA
To output pulse
trains,
a current of 10mA
or more needs to
be passed.
Pulse frequency
range:
38 1600Hz
250Vac-1A
(cosφ=1)
: at resistance load
30Vdc-0.5A
250Vac-0.5A
(cosφ=0.4)
B-10
E6581158
Inverter internal circuits
5V
VIB
15k
15k
4.7K
+
-
FM
P24
V
FM
I
+
-
100
24V
P24
PTC
10
PTC
OUT
10
NO
24V
FLA
FLB
RY
FLC

Hide quick links: