Auto-Stop In Case Of Lower-Limit Frequency Continuous Operation - Toshiba TOSVERT VF-S11 Instruction Manual

New global standard inverter
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

6.8
Auto-stop in case of lower-limit frequency continuous
operation
6.8.1
Auto-stop in case of lower-limit frequency continuous
operation

: Auto-stop in case of lower-limit frequency continuous operation

• Function
If operation is carried out continuously at a frequency below the lower-limit frequency (
of time set with
"
" is displayed (alternately) on the operation panel.
This function will be canceled if a frequency command above the lower-limit frequency (
[Parameter setting]
Title
Auto-stop in case of lower-limit fre-
quency continuous operation time
Output frequency [Hz]
+0.2Hz
Operation signal (F-CC)
Note: This function is enabled even at the start of operation and during switching between forward and re-
verse run.
, the inverter will automatically slow down the motor to a stop. At that time,
Function
F-27
Adjustment range
0.0: None
0.1-600.0 (sec.)
E6581158
) for the period
).
Default setting
6
0.0
Time [s]
ON
OFF