Power factor improving capacitor
Power factor improving capacitors cannot be installed on the output side of the inverter. When a motor
is run that has a power factor improving capacitor attached to it, remove the capacitors. This can cause
inverter malfunction trips and capacitor destruction.
Inverter
Operating at other than rated voltage
Connections to voltages other than the rated voltage described in the rating label cannot be made. If a
connection must be made to a power supply other than one with rated voltage, use a transformer to
raise or lower the voltage to the rated voltage.
Circuit interrupting when two or more inverters are used on the same power line.
MCCB1
There is no fuse in the inverter's main circuit. Thus, as the diagram above shows, when more than one
inverter is used on the same power line, you must select interrupting characteristics so that only the
MCCB2 will trip and the MCCB1 will not trip when a short occurs in the inverter (INV1). When you can-
not select the proper characteristics install a circuit interrupting fuse between the MCCB2 and the INV1.
If power supply distortion is not negligible
If the power supply distortion is not negligible because the inverter shares a power distribution line with
other systems causing distorted waves, such as systems with thyristors or large-capacity inverters, in-
stall an input reactor to improve the input power factor, to reduce higher harmonics, or to suppress ex-
ternal surges.
U
V
W
Remove the power factor improving
capacitor and surge absorber
Power factor improving capacitor
(circuit interupting fuse)
MCCB2
MCCB3
MCCBn+1
Breaking of selected inverter
A-19
E6581158
IM
INV1
INV2
INVn