Toshiba TOSVERT VF-S11 Instruction Manual page 39

New global standard inverter
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

• Install EMC plate and shielded wires fit with the EMC plate.
Installing more than one unit in a cabinet
If you are installing two or more inverters in one cabinet, pay attention to the following.
• Inverters may be installed side by side with each other with no space left between them.
• When installing inverters side by side, detach the caution label on the top surface of each inverter and
use them where the ambient temperature will not rise above 40°C.
When using inverters where the ambient temperature will rise above 40°C, leave a space of 5 cm or
more between them and remove the caution label from the top of each inverter, or operate each inverter
at a current lower than the rated one. For more information, refer to "Load Reduction and Thermal Envi-
ronment Instruction Manual."
• Ensure a space of at least 20 centimeters on the top and bottom of the inverters.
• Install an air deflecting plate so that the heat rising up from the inverter on the bottom does not affect the
inverter on the top.
EMC plate
Ventilation fan
Inverter
Air deflecting plate
Inverter
A-27
E6581158
1

Hide quick links: