Jog run mode

• Function
Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal fenerates a jog
run frequency output at once, irrespective of the designated acceleration time.
Also, you can choose an operation panel start/stop mode between the ordinary start/stop mode and the
jog run start/stop mode.
The jog run function needs to be assigned to an input terminal. When assigning it to the RES terminal, set
The motor can be operated in jog mode while the jog run setting terminals are connected (RES-CC ON). (Setting
6
[Parameter setting]
Title
[Setting of jog run setting terminal (RES-CC)]
Assign control terminal RES ([4: reset signal] in default setting) as the jog run setting terminal.
Title
Note 1: During the jog run mode, there is LOW (low speed detection signal) output but no RCH (designated
frequency reach signal) output, and PID control does not work.
Note 2: When the operation panel only is used for operation in jog run mode, the jog run function does not need to
be assigned to any input terminal.
: Jog run frequency
: Jog run stopping pattern
: Panel jog run mode
to
.
to
.)
Function
Jog run frequency
Jog run stopping
pattern
Panel jug run mode
Function
Input terminal selection (RES)
Adjustment range
-20.0 (Hz)
0: Slowdown stop
1: Coast stop
2: DC braking
0: Disabled
1: Panel jog run mode enabled
Adjustment range
0-64
F-28
E6581158
Default setting
5.0
0
0
Default setting
4
(jog run setting
terminal)