Toshiba TOSVERT VF-S11 Instruction Manual page 256

New global standard inverter
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

[Alarm information]
Error code
/
13
Note) When the ON/OFF function is selected for DC braking (DB), using the input terminal selection parameter,
Each message in the table is displayed to give a warning but does not cause the inverter to
trip.
Problem
• The ST-CC circuit is opened.
ST terminal OFF
• The supply voltage between R, S and T is
Undervoltage in main
circuit
• The inverter is n the process of retry.
Retry in process
• A momentary stop occurred.
• The frequency setting signals at points 1
Frequency point set-
ting error alarm
• This message is displayed when pressing
Clear command ac-
ceptable
• The operation panel is used to stop the
Emergency stop
command accept-
able
• An error is found in a setting when data is
Setting error alarm /
An error code and
data are displayed
alternately twice
each.
• The first and last data item in the
Display of first/last
/
data items
• DC braking in process
DC braking
• Motor shaft fixing control is in process.
Shaft fixing control
• The number of digits such as frequencies
Flowing out of ex-
cess number of digits
• The slowdown stop prohibition function
Momentary power
failure slowdown
stop prohibition func-
tion activated.
• The automatic stop function selected with
Auto-stop because of
continuous operation
at the lower-limit fre-
quency
• Parameters are being initialized to default
Parameters in the
process of initializa-
tion
• The RUN or STOP key is held down for
Operation panel key
fault
• The RUN or STOP key is faulty.
• Auto-tuning in process
Auto-tuning
you can judge the inverter to be normal if
and CC.
Possible causes
under voltage.
and 2 are set too close to each other.
the STOP key while an error code is dis-
played.
operation in automatic control or remote
control mode.
reading or writing.
data group is displayed.
is more than 4.
(The upper digits have a priority.)
set with
(momentary power fail-
ure ride-through operation) is activated.
was activated.
values.
more than 20 seconds.
disappears when opening the circuit between the terminal
M-4
E6581158
Remedies
• Close the ST-CC circuit.
• Measure the main circuit supply voltage.
If the voltage is at a normal level, the
inverter requires repairing.
• The inverter is normal if it restarts after
several tens of senconds.
The inverter restarts automatically. Be
careful of the machine because it may
suddenly restart.
• Set the frequency setting signals at points
1 and 2 apart from each other.
• Press the STOP key again to clear the
trip.
• Press the STOP key for an emergency
stop.
To cancel the emergency stop, press any
other key.
• Check whether the setting is made cor-
rectly.
• Press MODE key to exit the data group.
• The message goes off in several tens of
seconds if no problem occurs. Note)
• Normal if the message disappears when
a stop command is entered (or the opera-
tion command is canceled).
• Lower the fequency free unit magnifica-
tion
.
• To restart operation, reset the inverter or
input an operation signal again.
• To deactivate the automatic stop function,
increase the frequency command above
the lower-limit frequency (LL) + 0.2 Hz or
turn off the operation command.
• Normal if the message disappears after a
while (several seconds to several tens of
seconds).
• Check the operation panel.
• Normal if it the message disappears after
a few seconds.