Maximum Frequency; Upper Limit And Lower Limit Frequencies - Toshiba TOSVERT VF-S11 Instruction Manual

New global standard inverter
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

The inverter was factory-configured by default so that shorting terminals F-CC and terminals R-CC si-
multaneously would cause the motor to slow down to a stop. Using parameter
can choose between stop and reverse run.
Using the parameter
This function is valid only when
5.8

Maximum frequency

: Maximum frequency
• Function
1) Programs the range of frequencies output by the inverter (maximum output values).
2) This frequency is used as the reference for acceleration/deceleration time.
Output frequency
80Hz
60Hz
If
is increased, adjust the upper limit frequency
Parameter setting
Title
Maximum frequency
5.9

Upper limit and lower limit frequencies

: Upper limit frequency
: Lower limit frequency
• Function
Programs the lower limit frequency that determines the lower limit of the output frequency and the upper
limit frequency that determines the upper limit of that frequency.
, however, you can select between forward run and reverse run.
is set to
(Hz)
0
100%
Function
E-15
(operation panel).
When
=80Hz
This function determines the value
in line with the ratings of the motor
and load.
Maximum frequency cannot be
When
=60Hz
adjusted during operation.To
adjust, first stop the inverter.
Frequency setting signal (%)
as necessary.
Adjustment range
30.0-500.0 (Hz)
E6581158
, however, you
5
Default setting
80.0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents