Toshiba TOSVERT VF-S11 Instruction Manual page 53

New global standard inverter
Hide thumbs Also See for TOSVERT VF-S11:
Table of Contents

Advertisement

Logic switching/Voltage-current output switching (slide switch)
(1)
(2)
2
Logic switching
Use SW1 to switch between logics.
Switch between logics before wiring to the inverter and without supplying power. If switching between
sink, source and PLC is done when power is turned on after switching or when the inverter is supplied
with power, the inverter might become damaged. Confirm it before supplying power.
Voltage-current output switching
Use the FM switch to switch between voltage output and current output.
Switch the FM terminal's voltage-current output before wiring to inverter or without supplying power.
Factory default settings of slide switches
SW1 : SINK side (WN, AN type)
SOURCE side (WP type)
FM : V side
VIA : V side
*
After you have selected a logic between sink and source, take measures to prevent the logic from
being changed.
SOURCE
PLC
SINK
B-14
E6581158
Vside
Vside
Iside
Iside

Hide quick links:

Advertisement

Table of Contents
loading