Minimum unit of frequency adjustment
If
steps of 0.11Hz.
6.6

Operation frequency

6.6.1

Starting frequency

: Starting frequency setting
• Function
The frequency set with
Use the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title
Starting frequency setting
(Frequency free unit magnification) is set to 1.00, the output frequency can be adjusted in
is put out as soon as operation is started.
parameter when a delay in response of starting torque according to the
Function
Output frequency [Hz]
Starting frequency setting
0
F-23
Adjustment range
0.5-10.0 (Hz)
E6581158
6
Default setting
0.5
Time [s]