Table of input terminal functions 3
Function
Code
No.
54
STN
Inversion of ST (coasting)
55
RESN
Inversion of RES
56
F+ST
Combination of forward run and standby
57
R+ST
Combination of reverse run and standby
58
AD3
Acceleration/deceleration 3 selection
59
F+AD3
Combination of forward run and
acceleration/deceleration 3
60
R+AD3
Combination of reverse run and
acceleration/deceleration 3
61
OCS2
Forced switching of stall prevention level 2
62
HDRY
Holding of RY-RC terminal output
63
HDOUT
Holding of OUT-NO terminal output
64
PRUN
Cancellation (clearing) of operation command from
panel
Table of output terminal functions 1
Function
Code
No.
0
LL
Frequency lower limit
1
LLN
Inversion of frequency lower limit
2
UL
Frequency upper limit
3
ULN
Inversion of frequency upper limit
4
LOW
Low-speed detection signal
5
LOWN
Inversion of low-speed detection signal
6
RCH
Designated frequency attainment signal
(completion of acceleration/deceleration)
7
RCHN
Inversion of designated frequency attainment
signal (inversion of completion of
acceleration/deceleration)
8
RCHF
Set frequency attainment signal
9
RCHFN
Inversion of set frequency attainment signal
10
FL
Failure signal (trip output)
11
FLN
Inversion of failure signal (inversion of trip output)
Function
ON: Coast stop (gate off)
OFF: Ready for operation
ON: Acceptance of reset command
OFF→ ON: Trip reset
ON: Simultaneous input from F and ST
ON: Simultaneous input from R and ST
ON: Acceleration/deceleration 3
OFF: Acceleration/deceleration 1 or 2
ON: Simultaneous input from F and AD3
ON: Simultaneous input from R and AD3
ON: Enabled at the value of
OFF: Enabled at the value of
ON: Once turned on, RY-RC are held on.
OFF: The status of RY-RC changes in real time
ON: Once turned on, OUT-NO are held on.
OFF: The status of OUT-NO changes in real time
0: Operation command canceled (cleared)
1: Operation command retained
Function
ON: The output frequency is above the
OFF: The output frequency is equal to or less than
Inversion of LL setting
ON: Output frequency is equal to or higher than
OFF: Output frequency is lower than
Inversion of UL setting
ON: Output frequency is equal to or higher than
OFF: Output frequency is lower than
Inversion of LOW setting
ON: The output frequency is equal to or less than
OFF: The output frequency is above the specified
Inversion of RCH setting
ON: The output frequency is equal to or less than
OFF: The output frequency is above the frequency
Inversion of RCHF setting
ON: When inverter is tripped
OFF: When inverter is not tripped
Inversion of FL setting
K-17
E6581158
Action
according to conditions.
according to conditions.
Action
value.
the
set value.
value.
value.
value.
the specified frequency ± frequency set with
.
frequency ± frequency set with
the frequency set with
± frequency
set with
.
set with
± frequency set with
.
set
value.
11
.