3–54
"C" Group: Intelligent Terminal Functions
Func.
Name
Code
C031 Terminal [11] active
state
C032 Terminal [12] active
state
C033 Terminal [13] active
state
C034 Terminal [14] active
state
C035 Terminal [15] active
state
C036 Alarm relay terminal
active state
Option
Terminal
Code
Symbol
00
RUN
01
FA1
02
FA2
03
OL
04
OD
05
AL
"C" Function
Description
Select logic convention,
two option codes:
00 normally open N.O.
01 normally closed N.C.
Output Summary Table - This table shows all twenty-two functions for the logic output
terminals [11] – [15] at a glance. Detailed function descriptions, related parameters, settings,
and example wiring diagrams are in

Output Function Summary Table

Function Name
Run signal
Frequency arrival type
1 – constant speed
Frequency arrival type
2 – over-frequency
Overload advance
notice signal (1)
Output deviation for
PID control
Alarm signal
Defaults
Run
Mode
Edit
–FE
–FU
Lo Hi
(EU)
(US)
✘ ✔
00
00
✘ ✔
00
00
✘ ✔
00
00
✘ ✔
00
00
✘ ✔
00
00
✘ ✔
01
01
"Using Intelligent Output Terminals" on page
Description
ON
Inverter is in Run Mode, motor running
OFF
Inverter is in Stop Mode, motor stopped
ON
when output to motor is at the standard set frequency
F001
OFF
when output to motor is not at the set frequency F001
ON
when output to motor is at or above the FA
Threshold 1 (C042) during accel
OFF
when the output to motor is below the FA Threshold 1
(C043) during decel
ON
when output current is more than the set Threshold 1
for the overload signal (set with C041)
OFF
when output current is less than the set
Threshold 1for the overload signal
ON
when PID error is more than the set threshold for the
deviation signal
OFF
when PID error is less than the set threshold for the
deviation signal
ON
when the alarm condition has been met and not reset
OFF
when the alarm had not tripped since the previous
power cycle or since the previous keypad reset
SRW Display
Units
–FR
(JP)
00
>C031 OUT-TM
O/C-11
00
>C032 OUT-TM
O/C-12
00
>C033 OUT-TM
O/C-13
00
>C034 OUT-TM
O/C-14
00
>C035 OUT-TM
O/C-15
01
>C036 OUT-TM
O/C-AL
4–42.
NO
NO
NO
NO
NO
NC