Input Function Summary Table - Hitachi SJ200 Series Instruction Manual

Single-phase input 200v class; three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for SJ200 Series:
Table of Contents

Advertisement

Input Function Summary Table – This table shows all twenty-four intelligent input
functions at a glance. Detailed descriptions of these functions, related parameters and
settings, and example wiring diagrams are in
page
4–9.
Option
Terminal
Function Name
Code
Symbol
00
FW
Forward Run/Stop
01
RV
Reverse Run/Stop
02
CF1 *1
Multi-speed Select,
Bit 0 (LSB)
03
CF2
Multi-speed Select,
Bit 1
04
CF3
Multi-speed Select,
Bit 2
05
CF4
Multi-speed Select,
Bit 3 (MSB)
06
JG
Jogging
07
DB
External DC Braking ON
08
SET
Set (select) 2nd
Motor Data
09
2CH
2-stage Acceleration
and Deceleration
11
FRS
Free-run Stop
12
EXT
External Trip
"Using Intelligent Input Terminals" on

Input Function Summary Table

ON
Inverter is in Run Mode, motor runs forward
OFF
Inverter is in Stop Mode, motor stops
ON
Inverter is in Run Mode, motor runs reverse
OFF
Inverter is in Stop Mode, motor stops
ON
Binary encoded speed select, Bit 0, logical 1
OFF
Binary encoded speed select, Bit 0, logical 0
ON
Binary encoded speed select, Bit 1, logical 1
OFF
Binary encoded speed select, Bit 1, logical 0
ON
Binary encoded speed select, Bit 2, logical 1
OFF
Binary encoded speed select, Bit 2, logical 0
ON
Binary encoded speed select, Bit 3, logical 1
OFF
Binary encoded speed select, Bit 3, logical 0
ON
Inverter is in Run Mode, output to motor runs at
jog parameter frequency
OFF
Inverter is in Stop Mode
DC braking will be applied during deceleration
OFF
DC braking will not be applied
ON
The inverter uses 2nd motor parameters for
generating frequency output to motor
OFF
The inverter uses 1st (main) motor parameters
for generating frequency output to motor
ON
Frequency output uses 2nd-stage acceleration
and deceleration values
OFF
Frequency output uses standard acceleration and
deceleration values
ON
Causes output to turn OFF, allowing motor to
free run (coast) to stop
OFF
Output operates normally, so controlled deceler-
ation stops motor
ON
When assigned input transitions OFF to ON,
inverter latches trip event and displays E12
OFF
No trip event for ON to OFF, any recorded trip
events remain in history until Reset
SJ200 Inverter
Description
3–43