AC Power:
AC Voltage and Frequency:
•
120 VAC (100 - 127 VAC), 50 to 60 Hz single phase
•
230 VAC (220 - 240 VAC), 50 to 60 Hz single phase
•
Auto-ranging
Current:
Voltage
100 - 127 VAC
220 - 240 VAC
HP recommends the use of magnetic-type circuit breakers, which are capable of handling
large in-rush currents for short durations (10 to 12 milliseconds) and are rated adequately
for the steady state currents.
Power Consumption:
Incoming Voltage
AC RMS
Typical Power Consumption
100- 127 VAC
180 watts
200 - 240 VAC
180 watts
Heat Output:
•
615 BTU/hr.
Typical
Maximum
Operating
Operating Current
Current
1.5 A
2.3 A
0.8 A
1.2 A
In-Rush Current
21.7 A
42.9 A