Table 10
Disk Enclosure Electrical Requirements
Measurement
Voltage
– Range
– Frequency
Current
– Typical
Maximum Operating
– 100 - 120 V
– 200 - 240 V
– Maximum In-rush
*
In-rush current occurs for 10 to 12 milliseconds
HP recommends the use of magnetic-type circuit breakers, which are capable of handling large
in-rush currents for short durations (10 to 12 milliseconds) and are rated adequately for the
steady state currents.
Table 11
Recommended European Circuit Breakers*
Number of
Breaker
Components
Rating
1 to 3
16 amps
4
16 amps
*
Data assumes no other devices share the circuit breaker.
Circuit breaker rating must be adequate for the total current drawn by all devices on
Note
all electrical paths that share a circuit breaker.
Site Requirements
116
Value
220-240V
100 - 127V
50-60Hz
2.9 - 3.2A
2.6 - 3.2A
5.3 - 6.7A
20A
Breaker Type
Type C or Type D per IEC 898
or
Type K per IEC 947-2
Type D per IEC 898
or
Type K per IEC 947-2