Controller Enclosure Power Supply Fan Module

Introduction
This section describes procedures to troubleshoot the controller enclosure power supply
fan module. See
Figure
Troubleshooting Table" on page
Figure 82
Controller Enclosure Power Supply Fan Module
Servicing Notes
When replacing the power supply fan module, make sure you have the replacement
module available before removing the defective module. Once you remove the fan
module, you have approximately 15 minutes to install the new module. Operating the
disk array without a fan module for more than 15 minutes may cause a thermal
shutdown.