HP XP7 is configured for input power using separate rackmount PDU products. PDUs are available
for three phase or single phase power for NEMA and IEC compliance applications.
Table 26 HP XP7 AC PDU options
Product
Number
H6F71A
H6F73A
H6F70A
H6F72A
Notes
1.
Each PDU has one fixed power cord with attached plug. Power cord is not removable.
NOTE:
PDU models can be changed in the field using offline maintenance procedures.
NOTE:
When ordering systems, HP does not allow mixtures of different phase PDUs in a system
(even though there are no technical issues). Only upgrade orders can ship with difference phase
PDUs in a system.
80
Specifications
Number of
PDU per Rack
Local Power
3 phase (4
2
wire)
3 phase (5
2
wire)
single phase
4
NEMA
single phase
4
IEC
Branch circuit
requirements
1
per PDU
Plug Type
200-220V, 3Ø,
NEMA
4-wire, 30A
L15-30P
380-415V, 3Ø,
IEC60309 4
5-wire, 16A
pole, 5-wire
380-415VAC,
16A
200-240V, 1Ø,
NEMA L6-30P
3-wire, 30A
200-240V, 1Ø,
IEC60309 2
3-wire, 32A
pole, 3-wire,
240VAC, 32A
Facility
receptacle
needed
Notes
NEMA
For customers
L15-30R
with, 200 - 220
VAC, 3-Phase,
4-Wire Power
Distribution
System
IEC60309 4
For customers
pole, 5-wire,
with 380 - 415
380-415 VAC,
VAC,
16A
Three-Phase,
5-Wire Wye
Power
Distribution
System
NEMA L6-30R
For customers
with single
phase power
and need
NEMA L6-30P
plug
IEC60309 2
For customers
pole, 3-wire,
with single
240VAC, 32A
phase power
and need
IEC60309 32A
plug