HP Surestore Disk Array 12h - And FC60 Service Manual page 115

Hp surestore e disk array fc60 service manual
Hide thumbs Also See for Surestore Disk Array 12h - And FC60:
Table of Contents

Advertisement

Table 8
Total Operating and In-Rush Currents
Controller w/ 6 Disk Enclosures
Controller w/ 5 Disk Enclosures
Controller w/ 4 Disk Enclosures
Controller w/ 3 Disk Enclosures
Controller w/ 2 Disk Enclosures
Controller w/ 1 Disk Enclosure
*
In-rush current occurs for 10 to 12 milliseconds
Table 9
Controller Enclosure Electrical Requirements
Measurement
Voltage
– Range
– Frequency
Current
– Typical
– Maximum Operating
– Inrush
Operating
Operating
Current
Current
@ 110v
@ 220v
41.3A
34.8A
28.3A
21.8A
15.3A
8.8
Value @ 110v
Value @ 220v
100-127V
220-240V
50 - 60 Hz
50 - 60 Hz
1.5A
0.8A
2.3A
1.2A
21.4A
42.9A
*
In-Rush
Power
Current
Cords
20.4A
124A
17.2A
104A
14.0A
84A
10.8A
64A
7.6
44A
4.4A
24A
Site Requirements
14
12
10
8
6
4
115

Advertisement

Table of Contents
loading

This manual is also suitable for:

Surestore e disk array fc60

Table of Contents