Timer and Counter Instructions
200000
T0000
200001
T0001
200602
T0099
The loop in the program above has 4 input parameters which are used to start
all 100 timers with this common subroutine.
IR0
The PLC memory address of the timer's PV
IR1
The PLC memory address of the timer's Completion Flag
IR2
The PLC memory address of the timer's execution condition
D00000 The DM address of the word containing the timer's SV
The subroutine above is equivalent to the 400 instructions below.
Address
Instruction Operands
000000
LD NOT
200000
000001
TIM
0000
D00100
000002
LD
T0000
000003
OUT
200000
000004
LD NOT
200001
000005
TIM
0001
D00101
000006
LD
T0001
000007
OUT
200001
000008
LD NOT
200002
000009
TIM
0002
D00102
000010
LD
T0002
000011
OUT
200002
000396
LD NOT
200602
000397
TIM
0099
D00199
000398
LD
T0000
000399
OUT
200602
Section 3-6
291