Instruction Functions
Instruction
Symbol/Operand
Mnemonic
Code
CLEAR
CLI(691)
INTERRUPT
(Not supported
by CS1D CPU
Units for Duplex-
CPU Systems.)
CLI
N: Interrupt
@CLI
identifier
691
C: Control data
DISABLE INTER-
DI(693)
RUPTS
DI
@DI
693
ENABLE INTER-
EI(694)
RUPTS
EI
694
Clears or retains recorded interrupt inputs for I/O interrupts
or sets the time to the first scheduled interrupt for scheduled
N
interrupts.
C
N = 0 to 3
Interrupt
input n
Internal
status
Recorded interrupt cleared
N = 4 to 5
MSKS(690)
Time to first
scheduled interrupt
Disables execution of all interrupt tasks except the power OFF
interrupt.
Enables execution of all interrupt tasks that were disabled with
DI(693).
Function
Interrupt
input n
Internal
status
Recorded interrupt retained
Execution of scheduled
interrupt task.
Disables execution of all
interrupt tasks (except
the power OFF interrupt).
Disables execution of all
interrupt tasks (except the
power OFF interrupt).
Enables execution of all
disabled interrupt tasks.
Section 2-2
Location
Page
Execution
condition
Output
852
Required
Output
856
Required
Output
859
Not required
85