Table Data Processing Instructions
Description
Related Memory Area
Words
730
Area
Indirect DM/EM
addresses in binary
Indirect DM/EM
addresses in BCD
Constants
Data Registers
Index Registers
Indirect addressing
using Index Registers
MAX(182) searches the range of memory from R1 to R1+C–1 for the maxi-
mum value in the range and outputs that maximum value to D.
When bit 14 of C+1 has been set to 1, MAX(182) writes the PLC memory
address of the word containing the maximum value to IR00. (If two or more
words within the range contain the maximum value, the address of the first
word containing the maximum value is written to IR00.)
When bit 15 of C+1 has been set to 1, MAX(182) treats the data within the
range as signed binary data.
R1+(W–1)
Note MAX(182) can be processed in the background. Refer to the SYSMAC CS/
CJ/NSJ Series PLC Programming Manual (W394) for details.
Name
IR00 Output for
Background Execution
ER/AER Flag for
Background Execution
C
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Specified values only ---
---
---
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
PC memory
address
C words
Max.
value
Address
A595 and
When an index register is specified as the out-
A596
put for an instruction processed in the back-
ground, A595 and A596 receive the output
instead of IR00.
(A595 contains the rightmost digits, and A596
contains the leftmost digits.)
A39510
This flag is turned ON if an error or illegal
access occurs during background execution.
Section 3-17
R1
D
DR0 to DR15
C
W
Operation