Data Control Instructions
000000
TPO
S
C
R
3-18-7 SCALING: SCL(194)
Purpose
Ladder Symbol
Variations
Applicable Program Areas
Operands
796
TPO(685) takes the duty ratio in D00010, converts
that duty ratio to a time-proportional output, and
D00010
Duty ratio
outputs the pulse output to bit 00 of CIO 0001.
D00000
Parameters
000100
Pulse output
D00000
1
1
0
D00001
0
0
6
D00002
0
7
D
D00003
1
F
4
D00004
Do not set.
D00005
Do not set.
D00006
Do not set.
:
:
D00010
0 to 2710 hex
Converts unsigned binary data into unsigned BCD data according to the
specified linear function.
SCL(194)
S
P1
R
Variations
Immediate Refreshing Specification
Block program
areas
OK
The contents of the four words starting with the first parameter word (P1) are
shown in the following diagram.
0
Duty ratio input, read initial value, and enable output limit function.
4
Control period = 1.00 s
0
Output lower limit = 20.00%
0
Output upper limit = 80.00%
0 to 100.00%
S: Source word
P1: First parameter word
R: Result word
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported.
Step program
areas
OK
OK
Section 3-18
SCL(194)
@SCL(194)
Not supported.
Subroutines
Interrupt tasks
OK