Omron SYSMAC CJ - REFERENCE MANUAL 01-2008 Reference Manual page 419

Sysmac cs/cj/one nsj series programmable controllers
Table of Contents

Advertisement

Data Shift Instructions
Description
Flags
Precautions
Examples
380
Area
Index Registers
Indirect addressing
using Index Registers
ROLL(572) shifts all bits of Wd and Wd +1 including the Carry Flag (CY) to
the left (from rightmost bit to leftmost bit).
Name
Error Flag
ER
Equals Flag
=
Carry Flag
CY
Negative Flag
N
When ROLL(572) is executed, the Error Flag will turn OFF.
If as a result of the shift the contents of Wd and Wd +1 are zero, the Equals
Flag will turn ON.
If as a result of the shift the contents of the leftmost bit of Wd + 1 is 1, the Neg-
ative Flag will turn ON.
Note It is possible to set the Carry Flag contents to 1 or 0 immediately before exe-
cuting this instruction, by using the Set Carry (STC(040)) or Clear Carry
(CLC(041)) instructions.
When CIO 000000 is ON, word CIO 0100, CIO 0101 and the Carry Flag (CY)
will shift one bit to the left. The contents of CIO 010015 will be shifted to the
Carry Flag (CY) and the Carry Flag contents will be shifted to CIO 010000.
---
,IR0 to ,IR15
–2048 to +2047 ,IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Wd+1
Label
OFF
ON when the shift result is 0.
OFF in all other cases.
ON when 1 is shifted into the Carry Flag (CY).
OFF in all other cases.
ON when the leftmost bit is 1 as a result of the shift.
OFF in all other cases.
Wd
Wd+1: CIO 0101
Section 3-9
Wd
Wd
Operation
Wd: CIO 0100
Instruction executed once

Hide quick links:

Advertisement

Table of Contents
loading