Summer Compensation - Offset Of The Setpoint Temperature For The Entry Into Summer Compensation; Summer Compensation - (Upper) Exit Temperature For Summer Compensation; Summer Compensation - Offset Of The Setpoint Temperature For The Exit From Summer Compensation - Busch-Jaeger SD/U12.55.11-825 Manual

Hide thumbs Also See for SD/U12.55.11-825:
Table of Contents

Advertisement

The parameter is used to specify the lower outside temperature value up to which temperature
value the setpoint correction (summer compensation) is performed based on too high an
outside temperature.
Notice
This parameter is only available if the "Summer compensation" parameter is set
on "Yes".
8.18.135 Summer compensation - Offset of the setpoint temperature for the entry into summer
compensation
Options:
The parameter is used to specify how many degrees Kelvin the setpoint value will be increased
by during summer compensation when the lower temperature value is reached.
Typical values for summer compensation are:
20°C: lower outside temperature value
32°C: upper outside temperature value
0 K: lower setpoint offset
4 K: upper setpoint offset
That means that a flowing setpoint increase of 0 to 4 K occurs if the outside temperature
increases from 20°C to 32°C.
Notice
This parameter is only available if the "Summer compensation" parameter is set
on "Yes".

8.18.136 Summer compensation - (Upper) exit temperature for summer compensation

Options:
The parameter is used to specify the upper outside temperature value up to which temperature
value the setpoint correction (summer compensation) is performed based on too high an
outside temperature.
Notice
This parameter is only available if the "Summer compensation" parameter is set
on "Yes".
8.18.137 Summer compensation - Offset of the setpoint temperature for the exit from summer
compensation
Options:
The parameter is used to specify how many degrees Kelvin the setpoint value will be increased
by during summer compensation when the upper temperature value is reached.
Typical values for summer compensation are:
20°C: lower outside temperature value
Product manual 2CKA001473B5472
Control elements and application parameter
Setting option between 0 - 25
Setting option between 10 - 40
Setting option between 0 - 25
Application "Internal RTC"
│217