8.18.37 Cooling control - Extended settings
Options:
This parameter enables additional functions, e.g. "Basic stage cooling".
8.18.38 Basic stage cooling
Notice
Only available when the "Extended settings" parameter under "Cooling control"
is activated.
8.18.39 Basic stage cooling — Status object cooling
Options:
This parameter enables the "Status cooling" communication object.
8.18.40 Basic stage cooling — Mode of the control value
Options:
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
–
Normal: Value 0 means "Valve closed".
–
Inverse: Value 0 means "Valve open".
8.18.41 Basic stage heating - Control value difference for sending of heating control value
Options:
The control values of the 0 - 100% PI continuous controller are not transmitted after every
calculation. Instead, they are transmitted when the calculation results in a value that is different
enough to the previous sent value to make a transmission meaningful. This value difference
can be entered here.
Product manual 2CKA001473B5472
Control elements and application parameter
Deactivated
Activated
Deactivated
Activated
Normal
Inverse
2%
5%
10%
Send cyclic only
Application "Internal RTC"