Setpoint Adjustment - Setpoint Adjustment Master/Slave Via Communication Object; Setpoint Adjustment - Resetting Of The Manual Adjustment For Receipt Of A Basic Setpoint - Busch-Jaeger SD/U12.55.11-825 Manual

Hide thumbs Also See for SD/U12.55.11-825:
Table of Contents

Advertisement

8.18.99 Setpoint adjustment - Setpoint adjustment master/slave via communication object

Options:
This parameter is used to specify whether the setpoint adjustment for master/slave is carried
out via a temperature value or a 1-byte counter value.
8.18.100 Setpoint adjustment — Resetting of the manual adjustment for receipt of a basic
setpoint
Options:
Activating this parameter will cause the manual adjustment to be deleted and the new setpoint
value to be provided when a new value is received via the "Basic setpoint" object.
If the parameter is deactivated, the manual adjustment is added to the new base setpoint value.
Example: Previous base setpoint value of 21°C + manual adjustment of 1.5°C = 22.5°C. The
object receives a new basic setpoint of 18°C plus the previous manual adjustment of 1.5°C for a
total of 19.5°C.
Product manual 2CKA001473B5472
Control elements and application parameter
1-byte counter value
Relative temperature value
Absolute temperature value
Deactivated
Activated
Application "Internal RTC"
│206

Advertisement

Table of Contents
loading

Table of Contents