Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%,"PI PWM, On/Off" or "Fan coil".
8.18.42 Basic stage cooling — Cyclic sending of the control value
Options:
The current control value used by the device can be cyclically transmitted to the bus.
Notice
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On", "2-point 1 Byte, 0/100%", "PI continuous, 0-
100%" or "Fan coil".
8.18.43 Basic stage cooling — Hysteresis
Options:
The hysteresis of the two-point controller specifies the fluctuation range of the controller around
the setpoint value. The lower switching point is located at "Setpoint value minus hysteresis" and
the upper point is at "Setpoint value plus hysteresis".
Notice
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On" or "2-point 1 Byte, 0/100%".
8.18.44
Basic stage cooling — PWM cycle cooling (min)
Options:
In PI PWM, On/off the control value percentage values are converted into a pulse-interval
signal. This means that a selected PWM cycle will be divided into an on-phase and an off-phase
based on the control value. Accordingly, a control value output of 33% in a PWM cycle of 15
min. results in an On-phase of five minutes and an Off-phase of 10 min. The time for a PWM
cycle can be specified here.
Notice
This parameter is only available when the "Control value type" parameter is set
on "PI PWM, On/Off".
Product manual 2CKA001473B5472
Control elements and application parameter
00:01:00 - 01:00:00
Setting option between 0.3 - 25
00:01:00 - 01:00:00
Application "Internal RTC"