Diagnostics Via Process Image; Table 65: Diagnostics Via Process Image - WAGO 750-632 Manual

Proportional valve module wago i/o system 750/753
Hide thumbs Also See for 750-632:
Table of Contents

Advertisement

WAGO I/O System 750/753
750-632 Proportional Valve Module
10.7

Diagnostics via Process Image

Table 65: Diagnostics via Process Image

Bit
S1.READY
S1.ON
_TARGET
S0.ERR
_MOD
S0.ERR
_CH1
S0.ERR
_CH2
State
Explanation
0
Channel error
Setpoint value
0
error
General error in
1
the I/O module
Channel error,
1
channel 1
Channel error,
1
channel 2
Cause
Undervoltage
Short circuit, wire break,
overload
Overtemperature
Current is not yet
stabilized after a setpoint
change.
Current controller is
parameterized.
Undervoltage
Mailbox configured
incorrectly.
See bit "S1.READY"
See bit "S1.READY"
Version 1.3.1, valid from FW/HW-Version 01/01
Diagnostics 105
Remedy
Check supply voltage.
Check wiring.
Check temperature, note
"Current Reduction"
diagram
Evaluate independent of
application.
-
Check supply voltage.
Reset I/O module to
factory settings.
See bit "S1.READY"
See bit "S1.READY"
Manual