WAGO I/O System 750/753
750-632 Proportional Valve Module
11.4.2.8
Table 62, 63 (Dithering Valve 1, Valve 2)
Tables 62 and 63 are identically structured. As an example, Table 62 will be
explained for Valve 1 here.

Table 91: Parameters, Table 62 (Dithering, Valve 1)

Register
0
1
2
3
4
Name,
Bits
Type
Explanation
DG_
0 ... 15
PRESACLER,
INT16
DG_AMPL,
0 ... 15
UINT16
DG_RAMP_ON,
0 ... 15
UINT16
DG_RAMP_OFF,
0 ... 15
UINT16
Value/Range
(Default)
(Default: 1)
1 ... 250
(Default: 10)
0 ... 5000
(Default: 1000)
0 ... 10000
(Default: 1)
0 ... 10000
(Default: 1)
Version 1.3.1, valid from FW/HW-Version 01/01
Appendix 133
Description
(reserved)
Divisor for setting the
dither frequency
f = 250 Hz/
DG_PRESCALER
Divisor
f [Hz]
1
250.0
2
125.0
3
83.3
4
62.5
5
50.0
6
41.7
7
35.7
8
31.3
9
27.8
10
25.0
20
12.5
30
8.3
40
6.3
50
5.0
100
2.5
250
1.0
n * 0.01%
Dither amplitude
One LSB corresponds to
0.01% of the nominal
current
n * 0.01%
Start up ramp per ms
One LSB corresponds to
0.01% of the nominal
current per ms
n * 0.01%
Shut off ramp per ms
One LSB corresponds to
0.01% of the nominal
current per ms