Diagnostics Via Mailbox; Channel Error; Table 75: Channel Errors - WAGO 750-632 Manual

Proportional valve module wago i/o system 750/753
Hide thumbs Also See for 750-632:
Table of Contents

Advertisement

WAGO I/O System 750/753
750-632 Proportional Valve Module
11.3

Diagnostics via Mailbox

11.3.1

Channel Error

Table 75: Channel Errors

Error
Code
1000
1000
1001
5
1002
1003
1005
1006
1007
1008
6
6
7
7
8
8
141
Chan-
Event Qualifier
nel
Mode
Type
No.
1
APPDIS
ERROR
2
APPDIS
ERROR
128
APPDIS
WARN
128
APPDIS
ERROR
0
APPDIS
ERROR
0
APPDIS
ERROR
1
SINGLE
WARN
2
SINGLE
WARN
1
APPDIS
ERROR
2
APPDIS
ERROR
1
APPDIS
ERROR
2
APPDIS
ERROR
1
SINGLE
WARN
2
SINGLE
WARN
1
SINGLE
WARN
2
SINGLE
WARN
1
SINGLE
WARN
Cause of Error
Diagnostics of the output stage,
channel 1
short circuit, overtemperature,
undervoltage
Diagnostics of the output stage,
channel 2
short circuit, overtemperature,
undervoltage
I/O module temperature > 97°C Switch off output stage.
I/O module temperature
> 102°C
Limit switch DI1 actuated
Limit switch DI2 actuated
Limit switch position exceeded.
Limit switch position exceeded.
Error on local bus:
substitute value strategy active
Error on local bus:
substitute value strategy active
Wire break error
Channel 1
Wire break error
Channel 2
Range exceeded, current
controller channel 1.
Maximum 2.0 A has been
exceeded.
Range exceeded, current
controller channel 2.
Maximum 2.0 A has been
exceeded.
Range underrun, current
controller channel 1.
Maximum 2.0 A has been
underrun.
Range underrun, current
controller channel 2.
Maximum 2.0 A has been
underrun.
Range exceeded, setpoint value
channel 1
Version 1.3.1, valid from FW/HW-Version 01/01
Appendix 117
Solution
Check 24 V supply.
Check for short circuit.
Check 24 V supply.
Check for short circuit.
Maintain current carrying
capacity curve.
Switch off output stage.
Maintain current carrying
capacity curve.
Critical error.
System shut down.
Critical error.
System shut down.
Reduce setpoint value.
Reduce setpoint value.
Switch to "JOG Mode".
Return to "Automatic
Mode".
Switch to "JOG Mode".
Return to "Automatic
Mode".
Check connections.
Check connections.
Reduce setpoint value.
Reduce dither amplitude.
Reduce setpoint value.
Reduce dither amplitude.
Increase setpoint value.
Increase dither
amplitude.
Increase setpoint value.
Increase dither
amplitude.
Smaller setpoint value,
equal to 100%