5.3.3

"Tip Mode"

The "Tip mode" function is a variant of the "Jog mode" function. In this case, the
change in current is not controlled by level. At a rising edge, the current is
increased or decreased for a parameterizable time period.
In this operating mode, the I/O module changes the control value by a fixed
amount, independent from the duration of the applied signal. For example, a
drive runs for a previously defined time in a fixed direction, and then stops,
regardless of how long a corresponding button is activated.

Figure 12: Tip Mode

Table 25: Tip Mode

No.
Event
1
Set SPL_EN to "0"
2
3
Set JOG_POS to "1"
Set JOG_NEG to "1"
4
Set JOG_POS to "1"
5
Set JOG_NEG to "1"
Do not exceed minimum or maximum values!
As soon as the control value ±100 % has been achieved, no other change
occurs.
Function Description
Description/Behavior
"Jog mode" is activated.
Present current level is maintained.
Present current level is increased for the time
T parameterized in PH_TIP_TIME.
Present current level is reduced for the time T
parameterized in PH_TIP_TIME.
Present current level is maintained.