WAGO-I/O-SYSTEM 750
750-632 Proportional Valve Module
10.7
Diagnostics via Process Image
Table 65: Diagnostics via Process Image
Bit
S1.READY 0
S1.ON
_TARGET
S0.ERR
_MOD
S0.ERR
_CH1
S0.ERR
_CH2
Pos : 109 /Dokumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.3.0, valid from FW/HW-Version 01/01
State
Explanation
Channel error
Setpoint value
0
error
General error in
1
the I/O module
Channel error,
1
channel 1
Channel error,
1
channel 2
Cause
Undervoltage
Short circuit, wire break,
overload
Overtemperature
Current is not yet
stabilized after a setpoint
change.
Current controller is
parameterized.
Undervoltage
Mailbox configured
incorrectly.
See bit "S1.READY"
See bit "S1.READY"
Diagnostics
101
Remedy
Check supply voltage.
Check wiring.
Check temperature, note
"Current Reduction"
diagram
Evaluate independent of
application.
-
Check supply voltage.
Reset I/O module to
factory settings.
See bit "S1.READY"
See bit "S1.READY"