9.1.1.3.6 "Valve Adjustment" Menu Item; Figure 50: "Valve Adjustment" Menu Item; Table 61: "Valve Adjustment" Menu Item - WAGO 750-632 Manual

Proportional valve module wago i/o system 750/753
Hide thumbs Also See for 750-632:
Table of Contents

Advertisement

96
Commissioning

9.1.1.3.6 "Valve Adjustment" Menu Item

This menu item can be used for each valve to compensate for design-related
differences between the magnets and the valve.

Figure 50: "Valve Adjustment" Menu Item

Table 61: "Valve Adjustment" Menu Item

Option
Valve adaption
Enable
Trigger Threshold
Deadband
Compensation
# MIN:A/#MIN:B
Maximum Output
Signal
# MAX:A/#MAX:B
Nominal current
Manual
Version 1.3.1, valid from FW/HW-Version 01/01
Description
The valve adjustment is activated.
The valve adjustment is deactivated.
The response threshold can be entered in relation to the current range
selected. This parameter compensates for negative overlap.
The relationship between the inrush current to compensate for the dead
zone and the selected current range can be entered here. This parameter
compensates for positive overlap.
The relationship between the output current and the selected current
range can be limited here.
The nominal current for the valve can be entered here. The setpoint value
may not exceed the nominal current.
WAGO I/O System 750/753
750-632 Proportional Valve Module

Advertisement

Table of Contents
loading