WAGO I/O System 750/753
750-632 Proportional Valve Module
Table 31: Approach End Stop Value
No.
Event
1
Set SPL_EN to "0"
2
Set JOG_POS to "1"
Set JOG_POS to "0"
3
Set JOG_POS to "1"
4
Set DI to "1".
5
Set DI to "0".
6
Set JOG_POS to "0"
Set JOG_NEG to "1"
7
Set JOG_NEG to "0"
Set JOG_POS to "1"
8
9
Set DI to "1".
10
Set JOG_POS to "0"
11
Set JOG_POS to "1"
Set JOG_POS to "0"
12
Set DI to "0".
Description/Behavior
"JOG mode" is activated.
Present current level is maintained.
Present current level is increased.
Present current level is maintained.
Present current level is increased.
Rising ramp stops. Actual value drops until the
end stop value is reached. The actual value is
then frozen.
Present current level is maintained.
Present current level is maintained.
Present current level is reduced
Present current level is maintained.
Present current level is increased.
Rising ramp stops. Actual value drops until the
end stop value is reached. The actual value is
then frozen.
Present current level is maintained.
Present current level is increased
(even if the DI is still active).
Present current level is maintained.
Present current level is maintained.
Version 1.3.1, valid from FW/HW-Version 01/01
Function Description
Manual
49