126 Appendix
11.4.2.1
Channel-Dependent Parameters
11.4.2.2
Tables 50, 51 (Process Data Handling, Valve 1, Valve 2)
Tables 50 and 51 are configured identically. As an example, Table 50 will be
explained for Valve 1 here.
Table 85: Parameters, Table 50 (Process Data Handling, Valve 1)
Register Name,
1
2
3
4
5
6
7
8
Manual
Version 1.3.1, valid from FW/HW-Version 01/01
Bits
Type
Explanation
PH_SUBST_
0
STRA,
substitute value
BOOL
strategy
PH_SUBST_
0 ... 15
CURR,
INT16
PH_TIP_
0
MODE,
BOOL
PH_TIP_TIME,
0 ... 15
UINT16
PH_TARGET_
0 ... 15
WINDOW,
UINT16
PH_ENDSTOP
0 ... 2
_FUNCTION,
INT16
PH_ENDSTOP
0 ... 15
_CURRENT,
INT16
WAGO I/O System 750/753
750-632 Proportional Valve Module
Value/Range
Description
(Default)
0
Output last value from the
process image.
1
Output value according to
PH_SUBST_CURR.
-10000 ...
Substitute value for the output
+10000
current.
One LSB corresponds to 0.01%
of the maximum current.
0
JOG mode if activated in C1
1
TIP mode if activated in C1
0 ... 65535
In TIP mode, the current
(Default: 100)
increases according to the ramp
set, but according to the
maximum amount for the
duration set in PH_TIP_TIME
[Output in ms].
100
Window for status bit
ON_TARGET in % around the
setpoint; ON_TARGET is set if
the internal output value is
within the window around the
setpoint.
(Default: 18)
(reserved)
0 ... 6
End stop behavior:
(Default: 0)
0
Hold current value.
1
Approach end stop value
with stop ramp.
2
Approach end stop value
with ramp 1.
3
Approach end stop value
with ramp 2.
4
Approach end stop value
with ramp 3.
5
Approach end stop value
with ramp 4.
6
Approach end stop value
with ramp 5.
-10000 ...
End top value to be approached;
+10000
One LSB corresponds to 0.01%
(Default: 0)
of the permitted maximum
current.