Protocol 0X81 (Diagnostics); Table 71: Protocol 0X80, Structure Of Pdus, Legend; Table 72: Protocol 0X81, Description Of Services; Table 73: Protocol 0X81, Pdu Structure - WAGO 750-632 Manual

Proportional valve module wago i/o system 750/753
Hide thumbs Also See for 750-632:
Table of Contents

Advertisement

WAGO I/O System 750/753
750-632 Proportional Valve Module

Table 71: Protocol 0x80, Structure of PDUs, Legend

Description Description
-
TAB
REG
D1
D0
RSP
Note
Overlapping (concurrent) execution of confirmed services is
prohibited!
A confirmed service consists of the transmission of a request and the
reception of a reply. Overlapping execution of confirmed services is
prohibited. Once a service request has been transmitted, the reply must
first be received before a further request can be sent.
11.2.2

Protocol 0x81 (Diagnostics)

This protocol implements the transmission of diagnoses as an unconfirmed
service.

Table 72: Protocol 0x81, Description of Services

Service
Diagnostics
The table below shows the structure of PDUs for this protocol:

Table 73: Protocol 0x81, PDU Structure

Service PDU
Diagnostics
This byte is not used by this PDU
Table number
Register number
Parameter, top byte (MSB)
Parameter, bottom byte (LSB)
Reply status:
0x00
Executed successfully
0x01
Execution failed
0x02
Access denied
0x03
Table protected
0x04
Incorrect data length
0x05
Unknown table
0x06
Unknown register
[0x07...0xFF]
(reserved)
Description
Transmission of a diagnosis as a message.
Version 1.3.1, valid from FW/HW-Version 01/01
Structure of PDU (Bytes 0 ... 5)
0
1
2
0xFF EC1
EC0
Appendix 115
3
4
5
0x00
EQ
-
Manual