Tables 33, 34 (Di1, Di2); Table 83: Parameters, Table 33 (Di1) - WAGO 750-632 Manual

Proportional valve module wago i/o system 750/753
Hide thumbs Also See for 750-632:
Table of Contents

Advertisement

124 Appendix
11.4.1.4

Tables 33, 34 (DI1, DI2)

Tables 33 and 34 are configured identically. As an example, Table 33 will be
explained for DI1 here.

Table 83: Parameters, Table 33 (DI1)

Register Name,
0
1
2
Manual
Version 1.3.1, valid from FW/HW-Version 01/01
Bits
Type
Explanation
DI1_FILT,
0 ... 15
INT16
DI1_INVERT,
0
BOOL
Logic
DI1_FUNC,
0 ... 7
ENUM
WAGO I/O System 750/753
750-632 Proportional Valve Module
Value/Range
Description
(Default)
0 ... 65535
Filter time.
(Default: 10)
Using the filter suppresses
disturbing pulses. Input signals
with a pulse width shorter than
the filter time are not evaluated.
Specification as n * 100 µs
0 (Default)
Not inverted
1
Inverted
0 (Default)
Digital input
The status of the DI1 is only
displayed in the process image
and is not internally evaluated.
The value is inverted, depending
on Register 1. The inversion
takes place directly after the
filter. All further process steps
refer to this value.
Limit switch, Valve 1
1
Depending on the
parameterization of the end stop
behavior, the current actual
value is held or the end stop
value approached.
2
STOP Valve 1
Current setpoint value "0" is
approached with a STOP ramp,
for as long as the stop button is
pressed.
Note:
This function is state-controlled:
If the input is activated, the
"STOP" function is also
activated. The setpoint
value cannot be
approached.
If the input is deactivated,
the "STOP" function is also
deactivated. The current
setpoint value is
approached.