Hold Current Value ("Freeze"); Figure 18: Hold Current Value ("Freeze"); Table 32: Hold Current Value ("Freeze") - WAGO 750-632 Manual

Proportional valve module wago i/o system 750/753
Hide thumbs Also See for 750-632:
Table of Contents

Advertisement

50
Function Description

5.3.6.2.2 Hold Current Value ("Freeze")

Figure 18: Hold Current Value ("Freeze")

Table 32: Hold Current Value ("Freeze")

No.
Event
1
Set SPL_EN to "0"
2
Set JOG_POS to "1"
Set JOG_POS to "0"
3
Set JOG_POS to "1"
Set DI to "1".
4
5
Set DI to "0".
6
Set JOG_POS to "0"
Set JOG_NEG to "1"
7
Set JOG_NEG to "0"
8
Set JOG_POS to "1"
Set DI to "1".
9
Set JOG_POS to "0"
10
11
Set JOG_POS to "1"
Set JOG_POS to "0"
Set DI to "0".
12
Manual
Version 1.3.1, valid from FW/HW-Version 01/01
WAGO I/O System 750/753
750-632 Proportional Valve Module
Description/Behavior
"JOG mode" is activated.
Present current level is maintained.
Present current level is increased.
Present current level is maintained.
Present current level is increased.
Rising ramp stops. The actual value is frozen.
Present current level is maintained.
Present current level is maintained.
Present current level is reduced
Present current level is maintained.
Present current level is increased.
Rising ramp stops. The actual value is frozen.
Present current level is maintained.
Present current level is increased.
Present current level is maintained.
Present current level is maintained.