Function Description
5.3.7.3

Manual Mode in Case of Error (Emergency Operation)

Ensure the power supply via power jumper contacts and data contacts!
Emergency operation can only be ensured if the power supply is applied via the
power jumper contacts and data contacts. If one of the two power supplies is
interrupted, the I/O module cannot switch to emergency operation!
To ensure a durable power supply, for example, the 750-613 I/O module can only
be used for internal system supply.
Emergency operation is active once the substitute value strategy is applied and
the respective emergency operation parameters are set. Emergency operation is
deactivated when exiting the substitute value strategy.
While in emergency operation, local operation is implemented by the digital
inputs.
The digital inputs must be parameterized for JOG mode or TIP mode. The digital
inputs retain this parameterization regardless of the current operating mode.
The behavior can be configured as follows:
Section "Tables 52, 53 (Output Stage Valve 1, Valve 2)"
Section "Configuration and Parameterization with WAGO-I/O-CHECK"
Manual
Version 1.3.1, valid from FW/HW-Version 01/01
WAGO I/O System 750/753
750-632 Proportional Valve Module