Functions For The Setpoint Value Control; Automatic Mode; Figure 10: Automatic Mode; Table 23: Automatic Mode - WAGO 750-632 Manual

Proportional valve module wago i/o system 750/753
Hide thumbs Also See for 750-632:
Table of Contents

Advertisement

WAGO I/O System 750/753
750-632 Proportional Valve Module
5.3

Functions for the Setpoint Value Control

The I/O module offers the following functions, to be explained later:
5.3.1

"Automatic mode"

In "Automatic Mode", the I/O module approaches the specified setpoint value
automatically with the selected ramp.

Figure 10: Automatic Mode

Table 23: Automatic Mode

No.
Event
Set SPL_EN to "1"
1
2
Set RSEL
3
Change setpoint value
Set SPL_EN to "0"
4
Set SPL_EN to "1"
5
Description/Behavior
"Automatic mode" is activated.
Process data with continuously active ramps is
selected.
A change during a ramp is likewise possible.
Running ramp travel is interrupted and
continued using the new setpoint value.
Present current level maintained during a
ramp.
Running ramp travel is continued.
Version 1.3.1, valid from FW/HW-Version 01/01
Function Description
Manual
39